Powerware 6000 User Manual

Page 42

Advertising
background image

Installation

34

Powerware

®

9 Prestige Series User’s Guide (4500/6000 VA)

S

Rev H

www.powerware.com

Ground

TB1

TB2

Ground

Line 1

Input Connection

Output Connection

Input

Connections

REPO

Connections

Line 2/Neutral

Line 1

Line 2/Neutral

REPO Line 1
REPO Line 2

REPO Ground

Figure 11. Hardwired PPU Terminal Blocks

7. Determine your equipment’s grounding requirements according

to your local electrical code.

8. As part of the branch circuit that supplies this unit, install an

insulated grounding conductor. Use the following specifications
for the grounding conductor that connects to input ground
terminal TB1-1.
S

Material and insulation thickness:

must be identical to the

grounded and ungrounded branch-circuit supply conductors

S

Color:

consult local code requirements for ground wire color

code (usually green with or without a yellow stripe)

S

Ground:

should be grounded to the earth ground in the

service equipment or in the supply transformer (if supplied
by a separately-derived system)

NOTE All attachment plug-receptacles on, or connected to, the UPS or system
equipment must be a grounding type. The grounding conductors serving these
receptacles must be connected to the earth ground in the service equipment.