Powerware 6000 User Manual

Page 72

Advertising
background image

Communication

64

Powerware

®

9 Prestige Series User’s Guide (4500/6000 VA)

S

Rev H

www.powerware.com

SELECT LAN CONFIGURATION

1 >

NOVELL

ENTER SELECTION >+>

2

3

4

Q

>

>

>

>

AS400

3-COM/LAN MANAGER

CUSTOM CONFIGURATION

TO QUIT THIS MENU

Select the

AS400

option if you are using OnliSafe software to

monitor the UPS.

The

Custom Configuration

option has two screens: the first

screen has options available for inverter shutdown, and the
second screen has options available for the contact
configuration. Consult your shutdown software
documentation for details on the required signal states for
configuring LAN communications.

A > Inverter shutdown control is enabled active HIGH (+12V)

SELECT CUSTOM LAN CONFIGURATION

ENTER SELECTION >=>

B
C
Q

>
>
> TO QUIT THIS MENU

Inverter shutdown control is enabled active LOW (-12V)
Inverter shutdown control is disabled

Instructions: Choose the desired inverter shutdown function.

Warning: It is recommended that this feature should not be

used with normal RS-232 communications, conflicts may occur.

1 > UTIL_FAIL is active closed, LOW_BATT is active closed

SELECT CUSTOM LAN CONFIGURATION

ENTER SELECTION >=>

2
3
4
Q

>
>
>
>

UTIL_FAIL is active open, LOW_BATT is active closed
UTIL_FAIL is active closed, LOW_BATT is active open
UTIL_FAIL is active open, LOW_BATT is active open
TO QUIT THIS MENU

Instructions: Choose the desired contact configuration.