Installation

44

Powerware

®

9 Prestige Series User’s Guide (4500/6000 VA)

S

Rev H

www.powerware.com

9. Hardwire the input (TB1) and output terminations (TB2) for

the PPDM. See the following hardwired terminations table for
specifications. See Figure 17 for a detailed view of the terminal
blocks.

PPDM Hardwired Terminations

Wire Function

Terminal

Position

Terminal Wire

Size Rating

Suggested Wire

Size*

Conduit Connection

(Entry Size)

Input

L1

TB1-1

8 - 18 AWG

1 1/8

I (28 58 mm)

p

L2/Neutral

TB1-2

8 - 18 AWG

(10 - 0 mm

2

)

10 AWG

2

1 1/8

I (28.58 mm)

access hole for

Ground

TB1-3

10 - 18 AWG

(6 - 0 mm

2

)

(6 mm

2

)

3/4

I (19.05 mm)

conduit

Output

Model and Voltage
D

d

(

h

TB2-3

p

g

Dependent (see the
following Output

TB2-2

1 3/8

I (34.93 mm)

ollowing Output

Wiring Table)

TB2-1

6 - 18 AWG

(16 - 0 mm

2

)

8 AWG

(10 mm

2

)

/

(

)

access hole for

1

I (25 4 mm)

Neutral

TB2-4

(16 - 0 mm

2

)

(10 mm

2

)

1

I (25.4 mm)

conduit

Ground

TB2-5

*

**

*

Use 75

°C copper wire. Suggested wire size is based on Model 240: 120/240 hardwire full load ratings applied to NEC

Code Table 310-16.

PPDM Hardwired Models Output Wiring

Model 208:120/208

Model 240:120/240

Model 240:120/240E

Output Voltage

Terminal Position

Output Voltage

Terminal Position

Output Voltage

Terminal Position

120V

(50/60 Hz)

TB2-2 and TB2-4

and/or

100V, 110V,

TB2-2 and TB2-4

and/or

100V, 110V,

TB2 3 and TB2 4

127V

(60 Hz only)

and/or

TB2-3 and TB2-4

100V, 110V,
115V, or 120V

and/or

TB2-3 and TB2-4

100V, 110V,
115V, or 120V

TB2-3 and TB2-4

208V

(50/60 Hz)

TB2 1 and TB2 3

200V, 220V,

TB2 2 and TB2 3

200V, 220V,

TB2 1 and TB2 4

220V

(60 Hz only)

TB2-1 and TB2-3

200V, 220V,
230V, or 240V

TB2-2 and TB2-3

200V, 220V,
230V, or 240V

TB2-1 and TB2-4