Powerware 6000 User Manual

Page 35

Advertising
background image

Installation

27

Powerware

®

9 Prestige Series User’s Guide (4500/6000 VA)

S

Rev H

www.powerware.com

5. If additional battery cabinets are to be used, plug the battery

cord of the second cabinet into the battery connector of the first
cabinet after pivoting the battery connector guard out of the
way. Follow this procedure for each additional battery cabinet.

6. Remove the breaker tie from the circuit breaker on all battery

cabinets.

7. Select the correct UPS output voltage. Using a screwdriver, turn

the switch to the corresponding position of the output voltage
required (see Figure 5). The output voltage is factory-set to
220V.

C A U T I O N

Do not turn the Voltage Selector switch while the UPS is operating (see “Changing the
Output Voltage” on page 53). Changing the output voltage while the UPS is operating
may cause an emergency power-off.

Voltage
Selector
Switch

Figure 5. Voltage Selector Switch

8. The equipment to be protected by the UPS should be powered

off. Plug the equipment into the power output receptacle on the
PPU rear panel.

DO NOT protect laser printers with the UPS because of the
exceptionally high power requirements of the heating elements.

Advertising
This manual is related to the following products: