UPS Startup

To start up the UPS:

1. Verify the input breaker on the PPU rear panel is in the

OFF (O) position (see Figure 4 on page 26).

2. Confirm the correct UPS output voltage is selected (see Step 7

on page 27).

3. Turn on the equipment that is connected to the UPS.

4. If your PPU is a hardwired unit, supply utility power to the UPS

and skip to Step 7.

5. If your PPU is a plug/receptacle unit, plug the UPS power

supply cord into the power input connector on the PPU rear
panel.

6. Plug the other end of the power supply cord into a grounded,

three-wire, AC receptacle that has been wired in accordance
with NEC specifications or national wiring rules. See Chapter 6,
“Specifications” on page 69 for the input current/output voltage
requirements.

7. Switch the circuit breaker to the ON (

|

) position (see Figure 4

on page 26) on each battery cabinet connected to the PPU.

Each battery cabinet performs a self-test and then enters normal
operation. The battery cabinet startup should take about three
seconds.

8. Switch the PPU input breaker to the ON (

|

) position (see

Figure 4 on page 26).

The UPS performs diagnostic tests and enters Normal mode
with the equipment (load) offline. The

µ

indicator remains

lit. The startup should take about 15 seconds.

9. Press and hold the Output On button until you hear the UPS

beep (approximately one second).