33

Powerware

®

9 Prestige Series User’s Guide (4500/6000 VA)

S

Rev H

www.powerware.com

6. Hardwire the input (TB1-1 through TB1-3) and output

terminations (TB2) for the PPU. See the following hardwired
terminations table for specifications. See Figure 11 for a
detailed view of the terminal blocks.

PPU Hardwired Terminations

Wire Function

Terminal

Position

Terminal Wire

Size Rating

Suggested Wire

Size*

Conduit

Connection

(Entry Size)

Input

Ground

TB1-1

10 - 18 AWG

(6 - 0 mm

2

)

10 AWG

1 1/8

I (28.58 mm)

access hole for

L1

TB1-2

8 - 18 AWG

10 AWG

(6 mm

2

)

access hole for

3/4

I (19.05 mm)

L2/Neutral

TB1-3

8 - 18 AWG

(10 - 0 mm

2

)

(

)

/

(

)

conduit

Output

L1

TB2-1

8 - 18 AWG

1 1/8

I (28 58 mm)

p

L2/Neutral

TB2-2

8 - 18 AWG

(10 - 0 mm

2

)

10 AWG

2

1 1/8

I (28.58 mm)

access hole for

Ground

TB2-3

10 - 18 AWG

(6 - 0 mm

2

)

(6 mm

2

)

3/4

I (19.05 mm)

conduit

REPO

L1

TB1-4

7/8

I (22.23 mm)

L2

TB1-5

12 - 22 AWG

(4 - 0 mm

2

)

18 AWG

(0 75 mm

2

)

/

(

)

knock-out for

1/2

I (12 70 mm)

Ground

TB1-6

(4 - 0 mm

2

)

(0.75 mm

2

)

1/2

I (12.70 mm)

conduit

*

**

*

Use 75

°C copper wire. Suggested wire size is based on Model 6000 full load ratings applied to NEC Code Table 310-16.