Installation

45

Powerware

®

9 Prestige Series User’s Guide (4500/6000 VA)

S

Rev H

www.powerware.com

TB1

Input Connection

Output Connection

TB2

Neutral
Bonding
Jumper

TB2-1

TB2-2

TB2-3

Neutral

Ground

Line 1

Ground

Line 2/Neutral

Figure 17. Hardwired PPDM Terminal Blocks

NOTE Model 240: 120/240E only. The neutral bonding jumper on TB2 of the
PPDM grounds an output phase and may need to be removed. Refer to your local
electrical code requirements.

10. Determine your equipment’s grounding requirements according

to your local electrical code.

C A U T I O N

For PPDM systems with hardwired outputs, overcurrent protection and suitably rated
disconnect switches for the output AC circuit(s) are to be provided by either the
protected equipment or the customer’s distribution panel.