Battery times for the prestige 6000 – Powerware 6000 User Manual

Page 11

Advertising
background image

Introduction

3

Powerware

®

9 Prestige Series User’s Guide (4500/6000 VA)

S

Rev H

www.powerware.com

3. Add all of the resultant VA ratings together to obtain the total

load requirements of the equipment to be protected (see
Figure 2). If the load consists of the power-factor corrected
supplies, it is recommended to use total watts for the load
requirements.

3 COMPUTERS

3 MONITORS

EXTERNAL

MODEM

3 x 300 WATTS X 1.4 = 1260 VA

3 x 2 AMPS x 240V = 1440 VA

50 VA

1260 VA + 1440 VA + 50 VA = 2750 VA (Total Load Requirements)

300 WATTS

EACH

2 AMPS

EACH

50 VA

Figure 2. Volt-Amperes Calculation Example

If the total load requirements of the equipment exceeds the capacity of
the UPS, you must either reduce the number of pieces of equipment, or
use a UPS with a larger load capacity.

When deciding on which pieces of equipment to remove from the UPS,
select equipment that has a lower priority for power protection.
Computers, monitors, and modems typically have a higher priority
because they could be processing or transmitting data when a power
outage occurs.

Battery Times for the Prestige 6000

During a power failure, the UPS battery supplies power to your
equipment, providing time to complete computing activities prior to
UPS shutdown. The duration of this time period is directly related to the
UPS battery configuration. By adding battery cabinets, you can
customize the UPS to provide enough battery time for normal
processing activities.

Load (VA)

Load (W)

Average Battery Time (in Minutes)

Load (VA)

at 0.67 PF*

Load (W)

2 Cabinets 3 Cabinets 4 Cabinets 5 Cabinets 6 Cabinets

6000

4000

5

9

14

21

25

4500

3000

7

14

22

27

32

3000

2000

14

24

32

39

47

1500

1000

30

44

58

72

87

*

**

*

Typical Power Factor (PF)