Powerware 6000 User Manual

Page 69

Advertising
background image

Communication

61

Powerware

®

9 Prestige Series User’s Guide (4500/6000 VA)

S

Rev H

www.powerware.com

To access the front panel communication options, perform the following
steps:

1. If the UPS is powered on, prepare your equipment for

shutdown.

Press and hold the Output

Off button until the long beep

ceases (approximately three seconds).

The

µ

indicator remains lit indicating Normal mode, load

offline.

Switch the input breaker on the power processing unit to the
OFF (O) position. Wait until all indicators turn off and then
continue to the next step.

2. Switch the PPU input breaker to the ON (

|

) position while

pressing the Output

Off button until the alarm beeps. All

indicators begin flashing.

3. Press and hold the Output

Off button a second time until

the alarm beeps again.

A single indicator, corresponding with the current setting,
remains flashing.

4. Press the Output

Off button to scroll through the

communication options, top to bottom. Each time you press
the button, the UPS beeps and the next indicator flashes.

NOTE If you do not save a selection within two minutes, the setup automatically
aborts and switches back to the original configuration.

5. Press and hold the Output On button until the alarm beeps to

select and save a communication option. Failure to release the
button immediately after the beep will cause the UPS to abort
the setup.

6. Press the Output On button again to return the UPS to

Normal mode.

NOTE Printer mode selections are the only serial communication modes available
from the front panel.

Advertising