For long lead wire runs and in applications in electrically noisy
environments, it is recommended that twisted pair and/or shielded
wire be used. If shielded wire is used, the shield at the OMP-MODL
end should be connected to an external earth ground (Figure 3... -
30) or if available, a grounded Shield connection provided on
another type installed interface module (such as the MLIM-1).

Range

Excitation

Current

Range

Excitation

Current

Res 200 ohm

1 mA

Res 200,000 ohm

10 uA

Res 200 ohm

10 mA

Res 400,000 ohm

10 uA

Res 400 ohm

1 mA

RTD-100 ohm 300C

1 mA

Res 400 ohm

10 mA

RTD-100 ohm 850C

1 mA

Res 2000ohm

100 uA

RTD-1000 ohm 300C

100 uA

Res 4000 ohm

100 uA

RTD-1000 ohm 850C

100 uA

Res 10,000 ohm

100 uA

Therm -32 to 250C

10 uA

Res 20,000 ohm

100 uA

Therm -4 to 250C

10 uA

Res 40,000 ohm

10 uA

Therm +10 to 250C

10 uA

Res 100,000 ohm

10 uA

Therm +25 to 250C

100 uA

Excitation Currents used for MLIM-4 Ranges

2

1

12

11

10

9

8

7

6

5

4

3

RTD Element

Cable Shield

A

C

Jumper

+
+

-

-

Excitation leads

ML127

Sense leads

Connect Shield to an Earth Ground

Figure 3... -30: 4-Wire Configuration