Closed:

Low Ambient Mode allows the Low Ambient Cut-Out
to be programmed from 0 to 50 °F (-18 to 10°C). Val ues
above 25°F (-4°C) can be used to automatically shut
down the chiller when direct cooling methods be come
operational.

SWITCH 3: Refrigerant

Open:

The R-407C Mode MUST be selected for models us ing
refrigerant R-407C. Incorrect selection of this switch
may cause serious damage to the chiller.

Closed:

The R-22 Mode MUST be selected for models using
refrigerant type R-22. Incorrect selection of this switch
may cause serious damage to the chiller.

SWITCH 4: Unit Type

Open:

DO NOT USE THIS POSITION.

Incorrect programming may cause
damage to the chiller.

Closed:

Place the switch in the CLOSED position selects the
type of chiller as an air cooled chiller (YCAS). The
switch MUST always be in the CLOSED position.

Incorrect programming may cause
damage to the chiller.

S 1 - 2 A M B I E N T C O N T R O L

L O W A M B I E N T

S 1 - 3 R E F R I G E R A N T

R - 4 0 7 C

S 1 - 3 R E F R I G E R A N T

R - 2 2

Dip Switch Physical Location and Setting

FIG. 49

ENLARGED PHOTOGRAPH OF DIP

SWITCHES ON MICROPROCESSOR BOARD

LD03511A

LD03511B

“OPEN” Position:
Left side of switch
pushed in

“CLOSED” Position:
Right side of switch
pushed in

8

S 1 - 4 Y C W S

S 1 - 4 Y C A S

SWITCH 5: Motor Current Average option
(start-up)

Open:

DO NOT USE THIS POSITION.

Nuisance trips at start-up could result.

S 1 - 5 M O T O R C U R R E N T

A V E R A G I N G E N A B L E D

028981-G