Micro panel contents – York YCAS0130 User Manual

Page 182

Advertising
background image

182

YORK INTERNATIONAL

FORM 201.19-NM1 (204)

Micro Panel Contents

TABLE 7 – YCAS STYLE G, WYE DELTA START - 60 HZ.

MODEL

NO.

VOLTAGE

CODE

CHILLER

NAMEPLATE

RLA

NO. OF
LEADS

PER PHASE

100% FLA

OF SYSTEM

MP SET

POINT

VOLTAGE

130

17

246

*4

266

2.13

28

214

*2

231

3.71

40

130

2

140

3.89

46

107

2

116

3.20

58

86

2

93

2.58

140

17

267

*4

288

2.31

28

232

*4

251

2.00

40

140

2

151

4.20

46

116

2

125

3.46

58

93

2

100

2.8

150

SYS 1

17

295

*4

319

2.56

28

256

*4

276

2.22

40

155

2

167

4.64

46

128

2

138

3.84

58

103

2

111

3.09

150

SYS 2

17

265

*4

286

2.31

28

230

*4

248

2.00

40

139

2

150

4.18

46

115

2

124

3.44

58

92

2

99

2.75

160

17

295

*4

319

2.56

28

256

*4

276

2.22

40

155

2

167

4.64

46

128

2

138

3.84

58

103

2

111

3.09

170

SYS 1

17

321

*4

347

2.8

28

279

*4

301

2.42

40

169

*2

182

2.93

46

140

2

151

4.20

58

112

2

121

3.35

170

SYS 2

17

295

*4

319

2.56

28

256

*4

276

2.22

40

155

2

167

4.64

46

128

2

138

3.84

58

103

2

111

3.09

180

17

321

*4

347

2.8

28

279

*4

301

2.42

40

169

*2

182

2.93

46

140

2

151

4.20

58

112

2

121

3.35

* Indicates one lead/phase through motor protector.