ELECTRICAL DATA

SYSTEM #1 SYSTEM #2
MODEL

VOLTS

COMPRESSOR DATA FAN DATA

11, 12

COMPRESSOR DATA FAN DATA

11,12

YCAS

RLA X-LRA QTY FLA LRA RLA X-LRA QTY

FLA

LRA

(EA.) (EA) (EA) (EA)

0130EC

460 107 719 4 4.0 19.0 107 719 4 4.0 19.0

575 86 574 4 3.1 15.2 86 574 4 3.1 15.2

0140EC

460 116 719 4 4.0 19.0 116 719 4 4.0 19.0

575 93 574 4 3.1 15.2 93 574 4 3.1 15.2

0150EC

460 128 893 4 4.0 19.0 115 719 4 4.0 19.0

575 103 714 4 3.1 15.2 92 574 4 3.1 15.2

0160EC

460 128 893 4 4.0 19.0 128 893 4 4.0 19.0

575 103 714 4 3.1 15.2 103 714 4 3.1 15.2

0170EC

460 140 893 4 4.0 19.0 128 893 4 4.0 19.0

575 112 714 4 3.1 15.2 103 714 4 3.1 15.2

0180EC

460 140 893 4 4.0 19.0 140 893 4 4.0 19.0

575 112 714 4 3.1 15.2 112 714 4 3.1 15.2

0200EC

460 149 893 5 4.0 19.0 149 893 5 4.0 19.0

575 119 714 5 3.1 15.2 119 714 5 3.1 15.2

0210EC

460 163 893 5 4.0 19.0 149 893 5 4.0 19.0

575 130 714 5 3.1 15.2 119 714 5 3.1 15.2

0230EC

460 163 893 5 4.0 19.0 163 893 5 4.0 19.0

575 130 714 5 3.1 15.2 130 714 5 3.1 15.2