Technical data – York YCAS0130 User Manual

Page 88

Advertising
background image

88

YORK INTERNATIONAL

FORM 201.19-NM1 (204)

Technical Data

FIG. 26 – MODEL YCAS0200 - YCAS0230 DIMENSIONS (SI)

DIMENSIONS – YCAS0200 - YCAS0230 (SI)

All dimensions
are in mm un less
oth er wise not ed.

NOTES:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, re li able

operation and ease of maintenance. Site re stric tions may compromise min i mum clearances indicated below, resulting in un pre dict able air fl ow
pat terns and possible di min ished performance. YORK’s unit controls will optimize operation without nui sance high pres sure safety cutout;
however, the system designer must con sid er potential performance degradation. Access to the unit control center assumes the unit is no
higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; con trol panel end to wall - 1.2m;
top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be higher than the unit.

LD03751

LD03751a

2321

24 (EDGE OF

UNIT TO COOLER
CONNECTION)

457

VIEW A-A

MICRO-COMPUTER
CONTROL CENTER

OPTIONS PANEL

43

2235

COILS

SYS.#1

C

B

C

B

SYS.#2

COILS

CONTROL ENTRY
(8) 22 DIA. HOLES

VIEW B-B

Advertising