197

YORK INTERNATIONAL

FORM 201.19-NM1 (204)

PROCEDURE

WEEKL

Y

QUARTERL

Y

SEMI-ANNUALL

Y

YEAR

LY

EVER

Y

___ HOURS

Check oil level in oil separator sight glass

X

Check liquid line sight glass / moisture indicator

X

Record system operating pressures and temperatures

X

Check programmable operating setpoints and safety cutouts

and assure they are correct for particular application.

X

Check condenser coils for dirt/debris and clean if necessary

X

Check compressor superheat on evaporator and economizer

TXV’

s; Check condenser and economizer subcooling

1

X

Check compressor and evaporator heaters for operation

X

Sample compressor oil and replace oil if necessary

1

X

Leak check the chiller

1

X

Disconnect power source and lock out; Check tightness of

power wiring connections

1

X

MAINTENANCE REQUIREMENTS FOR

YORK

YCAS SCREW CHILLERS

*

* Reserved for customer use for any special site determined requirements.

1

This procedure must be performed at the speci

fi ed time interval by an Industry Certi

fi ed

Technician who has been trained and quali

fi ed to work on this type of

YORK

equipment.

A

record of this procedure being successfully carried out must be maintained on

fi le by the equipment owner should proof of adequate maintenance

be required at a later date for warranty validation purposes.

9

Advertising