Temperature and flows, Technical data – York YCAS0130 User Manual

Page 50

Advertising
background image

50

YORK INTERNATIONAL

FORM 201.19-NM1 (204)

TEMPERATURE AND FLOWS

(SI UNITS)

Technical Data

MODEL

NUMBER

YCAS

LEAVING WATER

TEMPERATURE (°C)

Evaporator FLOW

(l/s

3

)

AIR ON CONDENSER (°C)

MIN.

1

MAX.

2

MIN.

MAX.

MIN.

MAX

0130EC

4.4

12.8

8.7

33.1

-17.7

51.7

0140EC

4.4

12.8

8.7

33.1

-17.7

51.7

0150EC

4.4

12.8

12.6

37.9

-17.7

51.7

0160EC

4.4

12.8

12.6

37.9

-17.7

51.7

0170EC

4.4

12.8

12.6

37.9

-17.7

51.7

0180EC

4.4

12.8

12.6

37.9

-17.7

51.7

0200EC

4.4

12.8

15.8

47.3

-17.7

51.7

0210EC

4.4

12.8

15.8

47.3

-17.7

51.7

0230EC

4.4

12.8

15.8

47.3

-17.7

51.7

Excessive fl ow, above the max GPM,
will damage the evaporator.

NOTES:

1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK offi ce for application requirements.

2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK offi ce for application guidelines.

3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.