Section 11 - troubleshooting guide, Troubleshooting guide, Troubleshooting – York YCAS0130 User Manual

Page 200

Advertising
background image

200

YORK INTERNATIONAL

FORM 201.19-NM1 (204)

TROUBLESHOOTING GUIDE

Troubleshooting

PROBLEM POSSIBLE CAUSE ACTION

POSSIBLE CAUSE

ACTION

No display on panel - Main supply to control system OFF. Switch on main supply if safe to do so.
unit will not start

Emergency stop device off.

Check if control panel emergency stop switch

and any remote emergency stop devices are in
the OFF position. Turn to ON position (1) if safe
to do so.
CB3 tripped. Check CB3.
No supply to - T2. Check 115VAC to L & 2.
No 24VAC supply to power board. Check wiring from - T2 to powerboard and fuse.

No +12V output from powerboard.

Replace powerboard or isolate excessive load on

the board.
NO RUN PERM displayed

No liquid fl ow through the evaporator.

Ensure that liquid pumps are running. Valves are

(No run permissive) correctly set and fl ow is established.

Flow switch contacts are not made.

Check that the fl ow switch is functional and is

installed according to the manufacturer’s instructions.
Check cycling

contacts.

SYS # HIGH OIL TEMP Poor airfl ow through the condenser Check for airfl ow restrictions caused by blockages on
coils. intake faces of air coils.
Measured temperature incorrect. Check oil temp sensor and wiring.
Chiller FAULT: LOW Ambient air temperature is lower Use the ‘ambient temp.’ key to display the

AMBIENT TEMP displayed than the programmed operating temperature and confi rm that the displayed value is
limit. approximately correct. The warning message should
clear when the ambient air temperature rises above
the programmed operating limit.
Check the programmed settings are correct for the
options fi tted to the unit.
Measured temperature is incorrect. Check ambient sensor and wiring.
Chiller FAULT: HIGH Ambient air temperature is higher Use the ‘ambient temp.’ key to display the

AMBIENT TEMP displayed than the programmed operating limit. temperature and confi rm that the displayed value is
approximately correct. The warning message should
clear when the ambient air temperature falls below
the programmed operating limit.
Check that the programmed settings are correct for
the options fi tted to the unit.

Resid. heat is not being dissipated.

Check fans are operating correctly and the rotation is

correct. Check for airfl ow recirculation.
Measured temperature is incorrect. Check ambient sensor and wiring.
Chiller FAULT: LOW Leaving liquid drops below the Check for restrictions in the liquid fl ow line.
WATER TEMP displayed programmed low limit faster than the Check that the liquid fl ow is stable.
unit can unload.

Unit is not unloading.

Check the voltage to the unloader valve solenoid.

Check that the compressor unloads correctly.
Measured temperature is incorrect. Check water temp sensor and wiring.
Chiller FAULT: VAC Check main supply is stable and within allowable
UNDERVOLTAGE Poor main supply voltage. limits.
displayed. Check for voltage dip on compressor start.

Flow switch or cycling contacts are
not made.

Recirculated air is affecting the sensor.