York YCAS0130 User Manual

Page 171

Advertising
background image

171

YORK INTERNATIONAL

FORM 201.19-NM1 (204)

8

Program Value

Mode

Low Limit

High Limit

Default

Display Language

--

NA

NA

English

Discharge Pressure Cutout

--

200 PSIG

399 PSIG

399 PSIG

13.8 Bars

27.5 Bars

27.5 Bars

Discharge Pressure Unload

--

200 PSIG

399 PSIG

375 PSIG

13.8 Bars

27.5 Bars

25.9 Bars

Suction Pressure Cutout

Water Cooling

44.0 PSIG

70.0 PSIG

44.0 PSIG

3.03 Bars

4.83 Bars

30.3 Bars

Glycol Cooling

5.0 PSIG

70.0 PSIG

44.0 PSIG

0.34 Bars

4.83 Bars

3.03 Bars

High Ambient Air Temp Cutout

--

100.0 ºF

130.0 ºF

130.0 ºF

37.8 ºC

54.4 ºC

54.4 ºC

Low Ambient Ait Temperature Cutout

Standard

--

--

25.0 ºF

Ambient

--

--

-3.9

Low

0 ºF

50.0 ºF

25.0 ºF

Ambient

-17.8 ºC

10.0 ºC

-3.9 ºC

Leaving Chilled Liquid Temp Cutout

Water Cooling

--

--

36.0

--

--

2.2

Glycol Cooling

8.0 ºF

36.0 ºF

36.0 ºF

-13.3 ºC

2.2 ºC

2.2 ºC

Low Temp Glycol

-5.0 ºF

36.0 ºF

36.0 ºF

-20.5 ºC

2.2 ºC

2.2 ºC

High Motor Current Unload

--

30%

105%

100

Anti Recycle Time

--

300 sec

600 sec

600 sec

Local / Remote Mode

--

NA

NA

Local

Units Mode

--

NA

NA

Imperial

Lead / Lag Control Mode

--

NA

NA

Automatic

Power Failure Restart Mode

--

NA

NA

Automatic

Motor Current Averaging Cutout

--

30% FLA

110% FLa

70 % FLA

Suction Superheat Setpoint

EEV

9.0 ºF

15.0 ºF

12.0 ºF

5.0 ºC

8.3 ºC

6.6 ºC

The default values shown below are entered into
memory, when the program option is selected. The
list also provides the low and high limits the micro
will accept.