General periodic maintenance checks standard units – York YCAS0130 User Manual

Page 198

Advertising
background image

198

YORK INTERNATIONAL

FORM 201.19-NM1 (204)

GENERAL PERIODIC MAINTENANCE CHECKS

STANDARD UNITS

SERVICE SCHEDULE MINOR SERVICE

MAJOR SERVICE

All items under Minor Service plus:
Unit general: Check thermal insulation. Check main structure.
Check vibration isolators. Check paint-work.
Refrigerant systems general: Check relief valves. Check solenoid valves.
Check fusible plugs.
Check for pipework damage.
Check for leaks.
Check moisture indicator.
Check suction superheat.
Check economizer superheat.
Check liquid subcooling.
Compressors / Oil separator: Check oil level.
Check oil pressure.
Check slide valve operation.
Check compressor heater.
Check condition of oil.
Check discharge superheat.
Evaporator Check water fl ow. Check water pH / glycol strength.
Check water pressure drop.
Check heater.
Air cooled condensers: Check for airfl ow obstructions. Brush fi ns. Clean with mild, low
pH cleaner.
Check fi ns. Check fan motor bearings.
Check fans and fan guards.
Power & Control system general: Check panel condition. Check all connections.
Check mains and control wiring. Check compressor contactors.
Check sensor location. Check fan contactors / overloads.
Check mechanical HP cutouts. Check sensor / transducer calibration.
Check emergency stop. Check motor protectors.
Check overload devices.
Microprocessor controls: Check fault history. Check fan control function.
Check program settings. Check ambient cut-out function.
Check HP / LP cutout functions
Check pump-down function.
Check load / unload function.

Maintenance

Advertising