Ycas style g, across-the-line – 60 hz – York YCAS0130 User Manual

Page 19

Advertising
background image

19

YORK INTERNATIONAL

FORM 201.19-NM1 (204)

TABLE 1 – MOTOR PROTECTOR DIP SWITCH SETTING (CONT’D)

* Indicates one lead/phase through motor protector

2

YCAS STYLE G, ACROSS-THE-LINE – 60 HZ

MODEL

VOLT

CHILLER

NO.

MO TOR PROTECTOR

NO.

CODE

NAMEPLATE

LEADS

RLA

PER

MP

PHASE

DISPLAY

DIP SWITCH SETTINGS ON MP (“1” INDICATES ON)

HA XXX 128 64 32 16 8 4 2 1
17 321 *4 108 0 1 1 0 1 1 0 0

28 279 *4 94 0 1 0 1 1 1 1 0

180 40 169 *2 114 0 1 1 1 0 0 1 0
46 140 2 189 1 0 1 1 1 1 0 1
58 112 1 151 1 0 0 1 0 1 1 1
17 342 *4 115 0 1 1 1 0 1 0 0
28 298 *4 101 0 1 1 0 0 1 0 1
200 40 181 *2 122 0 1 1 1 1 1 1 0
46 149 2 201 1 1 0 0 1 0 0 1
58 119 1 161 1 0 1 0 0 0 0 1
17 374 *4 126 0 1 1 1 1 1 1 0

210

28 325 *4 110 0 1 1 0 1 1 1 0

SYS. 1

40 197 *2 133 1 0 0 0 0 1 0 1

46 163 *2 110 0 1 1 0 1 1 1 0
58 130 2 175 1 0 1 0 1 1 1 1
17 342 *4 115 0 1 1 1 0 1 0 0

210

28 298 *4 101 0 1 1 0 0 1 0 1

SYS. 2

40 181 *2 122 0 1 1 1 1 1 1 0

46 149 2 201 1 1 0 0 1 0 0 1
58 119 1 161 1 0 1 0 0 0 0 1
17 374 *4 126 0 1 1 1 1 1 1 0
28 325 *4 110 0 1 1 0 1 1 1 0
230 40 197 *2 133 1 0 0 0 0 1 0 1
46 163 *2 110 0 1 1 0 1 1 1 0
58 130 2 175 1 0 1 0 1 1 1 1