FIG. 24 – MODEL YCAS0130 - 0180 DIMENSIONS (SI)

Technical Data

DIMENSIONS – YCAS0130 - YCAS0180 (SI)

All dimensions
are in mm un less
oth er wise not ed.

LD03745a

NOTES:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reli-

able operation and ease of maintenance. Site re stric tions may compromise minimum clearances indicated below, resulting in un pre dict able
air fl ow patterns and possible diminished performance. YORK’s unit controls will optimize op er a tion without nuisance high pressure safety
cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; control panel end to wall - 1.2m;
top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be higher than the unit.

MODELS MODELS
DIMENSION 130 - 140 150 - 180
P 438 457

46 (EDGE OF

UNIT TO COOLER

CONNECTION