AMI with Spindle Control Reference Manual

15

Do not use the 115V AC connection for any other circuitry.

Note: If the existing emergency stop system is any other voltage than

115V AC, you must use the AMI as the power source (described

above) for the AMI emergency stop input.

Table Stop Test

The table stop test shows whether or not an emergency stop (E-stop) condition
has been detected or the internal switch has been pressed.

Reports on whether or not the system detects an emergency stop

condition. An E-stop condition can originate from the operator

console, Z-axis, or optional AMI.

Displays the status of the table stop button (Pressed or Released)

on the operator console.

If Z-axis control is enabled, a “Fault” or “No Fault” message
will appear. A fault indicates that at least one of the limit switch-
es on the spindle has been disengaged.

To display the table stop test:

From the Job Setup screen, select Installation
Setup and press

ENTER

. Then select the

Diagnostics screen and press

ENTER

again.

From the Diagnostics screen, highlight Table
Stop Test and press

ENTER

. The test will run

automatically.

When the test is complete, press the EXIT TEST softkey to close the “Table
Stop Test” screen.

Continue with Diagnostics or press the USE NEW SETTINGS softkey.

E-Stop

Signal
Status

Table Stop

Button

Z-Limit