Ex ia version, Electrical connection, Vegapuls 56 profibus pa 41 – VEGA VEGAPULS 56 Profibus PA User Manual

Page 41: Exd terminal compart- ment, Locking of the cover

Advertising
background image

VEGAPULS 56 Profibus PA

41

- +

2 1

Shield

Supply: 20 … 36 V DC, VBUS

1

2

- +

ESC

ESC

+

-

OK

OK

1

2

C

5

6

7

8

4

3

VBUS

Commu-
nication

+ -
4...20mA

Display

1

2

C

5

6

7

8

4

3

EEx d connection housing

(opening in Ex area not allowed)

Adjustment module and terminal com-
partment of display

(opening in Ex area permitted)

Exd terminal compart-
ment

1

/

2

“ NPT EEx d

diameter of the
connection cable
to the Exd
terminal com-
partment
3.1…8.7 mm
(0.12…0.34 inch)

Exd safe connection to the
Exd terminal compartment

1

/

2

“ NPT EEx d

diameter of the
connection cable
3.1…8.7 mm
(0.12…0.34 inch)

Exd version (loop-powered with pressure-tight encapsulated terminal compart-
ment)

Locking of the cover

ESC

ESC

+

-

OK

OK

-

+

1

2

C

5

6

7

8

4

3

VBUS

Commu-
nication

+ -
4...20mA

Display

1

2

C

5

6

7

8

4

3

Power supply and digital
measuring signal

To the indicating instrument in the
sensor lid or to the external indicating
instrument VEGADIS 50

M20x1.5
(diameter of the
connection cable
6…9 mm)

Ex ia version

Electrical connection

Power supply and digital
measuring signal

Spring-loaded terminals
(max. 2.5 mm

2

wire cross-

section)

Spring-loaded terminals
(max. 2.5 mm

2

wire cross-

section)

Sockets for connection of
VEGACONNECT 2 (communi-
cation sockets)