VEGA VEGAPULS 56 Profibus PA User Manual
Page 49
VEGAPULS 56 Profibus PA
49
Setup
• Click to the sensor or the measurement
loop on which you want to carry out the
parameter adjustment.
• Then click to "
OK
OK
OK
OK
OK“, the menu window "In-
strument data parameter adjustment“
opens.
Measurement loop data
• When clicking "
Meas. loop data
Meas. loop data
Meas. loop data
Meas. loop data
Meas. loop data“, the most
important measurement loop data will be
displayed.
Adjustment
("adjustment“ in chapter "6 Function dia-
gram).
• Click to "
Adjustment
Adjustment
Adjustment
Adjustment
Adjustment“.
• Click in the menu window "
Adjustment“ to
"
Min/Max-Adjustment
Min/Max-Adjustment
Min/Max-Adjustment
Min/Max-Adjustment
Min/Max-Adjustment“.
You can carry out the min./max. adjustment
"with medium“ (adjustment by means of the
real level) or
"without medium“ (without taking
the real level into account, i.e. with empty
vessel).
Generally, you will carry out the adjustment
without medium, so you are completely inde-
pendent of the actual vessel filling during the
adjustment. If you want to carry out the ad-
justment with medium, you have to carry out
the min. adjustment with emptied (also partly
emptied) vessel and the max. adjustment
with filled vessel (also partly filled vessel). It
is therefore easier and faster to carry out the
adjustment without medium.
• Click to "Quit
Quit
Quit
Quit
Quit“ and you are again in the
menu window "
Instrument data parameter
adjustment“.