Conditioning – VEGA VEGAPULS 56 Profibus PA User Manual

Page 68

Advertising
background image

68

VEGAPULS 56 Profibus PA

OK

+

or

100.0%

at

m (d)

XX.XXX

Setup

With the "

+“ or "–“ key you can

assign a level distance (ex-
ample 5.85 m) to the previ-
ously adjusted percentage
value. If you do not know the
distance, you have to do a
sounding.

The adjusted product dis-
tance is written in the sensor
and the display stops flash-
ing.

You thereby adjusted the lower product dis-
tance as well as the percentage filling value
corresponding to the lower product distance.

Note:

For level detection outside the operating range,
the operating range must be corrected accord-
ingly in the menu "

Sensor optimisation/Operat-

ing range“.

(max. adjustment)

Now you make the max. adjustment (upper
product distance) (example: 100 % and
1.270 m product distance). First enter the per-
centage value and then the product distance
corresponding to the percentage value.

Note:

The difference between the adjustment val-
ues of the lower product distance and the
upper product distance should be as big as
possible, preferably at 0 % and 100 %. If the
values are very close together, e.g. lower
product distance indication at 40 % (3.102 m)
and upper product distance adjustment at
45 % (3.331 m), the measurement will be
inaccurate. A characteristic curve is gener-
ated from the two points. Even the smallest
deviations between actual product distance
and entered product distance will consider-
ably influence the slope of the characteristic
curve. If the adjustment points are too close
together, small errors inflate to considerably
larger ones when the 0 % or the 100 % value
is outputted.

Adjustment with medium

Fill the vessel e.g. to 10 % and enter 10 % in
the menu "

Min. adjust“ with the "+“ and "–“

keys. Then fill the vessel, e.g. to 80 % or
100 % and enter 100 % in the menu "

Max.

adjust“ with the "+“ and "–“ keys.

5. Conditioning

Under the menu item "

Conditioning“, you

assign a product distance at 0 % and at 100
% filling. Then you enter the parameter and
the physical unit as well as the decimal point.

Enter in the menu window "

0 % corresponds“

the numerical value of the 0 % filling. In the
example of the adjustment with the PC and
the adjustment software VVO this would be
45 for 45 liters.

• Confirm with "

OK“.

With the "—>“ key you change to the 100 %
menu. Enter here the numerical value of your
parameter corresponding to a 100 % filling.
In the example 1200 for 1200 liters.

with
medium

Min.
adjust
at %

XXX.X

Max.
adjust
at %

XXX.X

Signal
condit-
ioning

Scal-
ing

0 %
corres-
ponds

XXXX

100 %
corres-
ponds

XXXX

Deci-
mal
point

888.8

prop.
to

Mass

Unit

Kg