7 Diagnosis
7.1 Simulation
To simulate a certain filling, you can call up
the function "Simulation“ on the adjustment
module MINICOM or in the software program
VVO.
With this function, you simulate a real vessel
filling level. Please note that connected instru-
ments, such as e.g. a PLC, react according
to their adjustments and will probably acti-
vate alarms or system functions.
7.2 Error codes
Error codes
Corrective measure
E013
No valid measured value
Message is displayed during the warm-up
- Sensor in the warm-up phase
phase
- Loss of the useful echo
If the message remains, a false echo storage
(with the adjustment software on the PC - see
"Echo curve“ under "Sensor optimisation“) must
be carried out together with a modification of
mounting location and orientation to achieve the
lowest possible false echo background.
E017
Adjustment span too small
Carry out a readjustment.
Make sure that the difference between
min. and max. adjustment is at least 10 mm .
E036
Sensor software does not run
Sensor requires a software update (service).
Message appears during a software update.
E040
Hardware failure/Electronics defec-
Check all connection cables.
tive
Contact our service department.
E113
Communication conflict
Service or sensor exchange
Simulation with VVO or PACTware
TM
If you start the simulation mode with the ad-
justment program VVO or PACTware
TM
on the
PC, the simulated level is outputted until you
quit the simulation mode.
Simulation with MINICOM
If you start the simulation mode on the adjust-
ment module MINICOM, the sensor returns to
standard operating mode after one hour.