7 Diagnosis

7.1 Simulation

To simulate a certain filling, you can call up
the function "Simulation“ on the adjustment
module MINICOM or in the software program
VVO.

With this function, you simulate a real vessel
filling level. Please note that connected instru-
ments, such as e.g. a PLC, react according
to their adjustments and will probably acti-
vate alarms or system functions.

7.2 Error codes

Error codes

Corrective measure

E013

No valid measured value

Message is displayed during the warm-up

- Sensor in the warm-up phase

phase

- Loss of the useful echo

If the message remains, a false echo storage
(with the adjustment software on the PC - see
"Echo curve“ under "Sensor optimisation“) must
be carried out together with a modification of
mounting location and orientation to achieve the
lowest possible false echo background.

E017

Adjustment span too small

Carry out a readjustment.
Make sure that the difference between
min. and max. adjustment is at least 10 mm .

E036

Sensor software does not run

Sensor requires a software update (service).
Message appears during a software update.

E040

Hardware failure/Electronics defec-

Check all connection cables.

tive

Contact our service department.

E113

Communication conflict

Service or sensor exchange

Simulation with VVO or PACTware

TM

If you start the simulation mode with the ad-
justment program VVO or PACTware

TM

on the

PC, the simulated level is outputted until you
quit the simulation mode.

Simulation with MINICOM

If you start the simulation mode on the adjust-
ment module MINICOM, the sensor returns to
standard operating mode after one hour.

Diagnosis