VEGA VEGAPULS 56 Profibus PA User Manual

Page 50

Advertising
background image

50

VEGAPULS 56 Profibus PA

• Confirm the adjustments with "

OK

OK

OK

OK

OK“ and

after a message is displayed, you are
again in the menu window "

Adjustment“.

Setup

• Choose "

no (adjustment without medium)

no (adjustment without medium)

no (adjustment without medium)

no (adjustment without medium)

no (adjustment without medium)“.

In the menu window "Min/Max-Adjustment“
you choose e.g. the level distance corre-
sponding to 100 % and 0 %. Of course, you
can also enter the distance values e.g. at
20 % and 75 % filling.

If the two points are too close together, e.g. at
45 % and 49 %, a considerable meas. error
can result, as the sensor generates by
means of the two adjustment points a linear
correlation between filling volume (%) and
meas. distance.

• Choose if you want to carry out the adjust-

ment in

meters (m) or in feet (ft).

• Enter a distance for the upper and lower

level and the extent of filling in % corre-
sponding to each distance.

In the example, the 0 % filling is at a product
distance of 5.850 m and the 100 % filling at a
product distance of 1.270 m.

Offset

See also A3-1 in chapter "6 Function dia-
gram“ under "Level Offset“.

Note:

The sensor is delivered with the sensor
measuring range set to the same value as
the operating range. After the sensor has
been adjusted, the operating range corre-
sponds to the adjustment range. The sensor
can only detect levels within the defined oper-
ating range. For level detection outside the
operating range (if you want to detect e.g.
108 % and -10 %), the operating range must
be corrected respectively in the menu "

Sen-

sor optimisation/Meas. environment“ (see the
following chapter "Sensor optimisation“,
"Meas. environment/Operating range“).

• Click in the menu window "

Adjustment“ to

"

Quit

Quit

Quit

Quit

Quit“.

You are again in the menu window "

Instru-

ment data parameter adjustment“.