3 technical data, 1 technical data – VEGA VEGASON 51P…53P Profibus PA User Manual

Page 16

Advertising
background image

16

VEGASON 51P … 53P

3 Technical data

3.1 Technical data

Power supply

Supply voltage

9 … 32 V DC

Power consumption

constant 10 mA (no leakage current output)

Output voltage U

O

of the segment coupler,

(depending on the segment coupler used)
see PA specification e.g.
- non Ex

e.g. 22 V DC (nominal voltage of the segment

coupler) max. 32 sensors on one two-wire
cable

- E x

13.5 V DC nominal voltage of the segment
coupler max. 10 sensors on one two-wire
cable (typically 8 sensors)

Cable load

dependent on the segment coupler, see
technical data of the segment couplers and
Profibus specification

Measuring range (reference plane is the transducer end)

Liquids

Solids

VEGASON 51

0.25 … 4 m

0.3 … 2 m

VEGASON 52

0.4 … 7 m

0.5 … 3.5 m

VEGASON 53

0.6 … 15 m

0.75 … 7 m

Output signal (see also "3.3 Data format of the output signal“)

digital (Profibus)

the digital output signal (meas. signal) is

modulated onto the power supply and further
processed in the PLC or in the process manage-
ment system

Integration time

0 … 999 seconds (adjustable)

Adjustment

- adjustment software VEGA Visual Operating on Master-Class 2 PC
- adjustment module MINICOM in the sensor or in the external indicating instrument (optio-

nal)

- process adjustment interface PACTware

TM

(VVO as subprogram)

- SIMATIC PDM in conjunction with Electronic Device Description (EDD)

Technical data