VEGA VEGASON 51P…53P Profibus PA User Manual
Page 18
18
VEGASON 51P … 53P
Technical data
Ambient conditions
Ambient temperature on the housing
-40°C … +80°C
Process temperature (transducer)
-40°C … +80°C (StEx: -20°C … +75°C)
Storage and transport temperature
-40°C … +80°C
Vessel pressure
- VEGASON 51, 52
-0.4 … 2.0 bar (absolute 3 bar)
- VEGASON 53
-0.4 … 1.5 bar (absolute 2.5 bar)
Protection
- sensor
IP 67
- transducer, process
IP 68
Protection class
II
Overvoltage category
III
Self-heating at 40°C
ambient temperature to
- sensor
45°C
- transducer, process
55°C
Ex technical data
Comprehensive data included in the attached approval documents (yellow binder)
Classification ia
intrinsically safe
Classification mark
II 1G EEx ia IIC T6 or II 2G EEx ia IIC T6
Ex approved
Zone 0, Zone 1 (ATEX)
Zone 0, Zone 1 (CENELEC, PTB, IEC)
Permissible ambient temperature
on the housing
- T6
-40°C … +42°C
- T5
-40°C … +58°C
- T4, T3
-40°C … +60°C
Permissible ambient temperature
on the transducer when used
in Ex areas
- T6
45°C
- T5
60°C
- T4
60°C
- T3
60°C
Process connections
VEGASON 51
G1
1
/
2
A, 1
1
/
2
“ NPT
VEGASON 52
G 2 A, 2“ NPT
VEGASON 52
DN 100 compression flange or mounting loop
Connection cables
Power supply
supply and signal via one two-wire cable
Electrical connection
spring terminals (max. 2.5 mm
2
)
Cable entry
2 x M20 x 1.5 (cable diameter 5 … 9 mm)
or 2 x
1
/
2
“ NPT (cable diameter
3.6 … 8.7 mm or 0.12 … 0.34 inch)
Ground connection
max. 4 mm
2