Software addressing – VEGA VEGASON 51P…53P Profibus PA User Manual
Page 39
VEGASON 51P … 53P
39
Electrical connection
Example 2
You want to set address 27.
16 + 8 + 2 + 1 = 27
You must set the DIP switches
5 = 16
4 = 8
2 = 2
1 = 1
to "ON“.
Example 3
You want to set address 99
64 + 32 + 2 + 1 = 99
You must set the DIP switches
7 = 64
6 = 32
2 = 2
1 = 1
to "ON“.
Software addressing
The DIP switches must be set to an address
of 126 … 255, i.e.
- either all DIP switches are set to "ON“,
corresponding to address 255 (delivery
status)
- or only DIP switch 8 is set to "ON“, corre-
sponding to address 128.
ON
Addr.
8 7 6 5 4 3 2 1
OFF
1
2
4
8
16
32
64
128
8 7 6 5 4 3 2 1
Of course, software addressing is also pos-
sible if the switches 7 … 2 are set to "ON“
(address 126).
Address assignment via software VVO is
described in chapter "6.2 Adjustment with
VVO“ under the heading "Software address-
ing“ or in chapter "6.3 Sensor adjustment with
the adjustment module MINICOM“.