Mounting and installation – VEGA VEGASON 51P…53P Profibus PA User Manual

Page 33

Advertising
background image

VEGASON 51P … 53P

33

Mounting and installation

1 m

2 m

3 m

4 m

5 m

5 m

10 m

15 m

B

A

max. meas.
distance

Distance of the
transducer to the
vessel wall

Curve 1 (liquids)

Curve 2 (solids)

Distance of the sensor from the vessel wall depend-
ing on the measuring distance (type 51 … 53)

If the sensor is mounted too close to the
vessel wall (dimension A in diagram), strong
false echoes can be caused. Buildup, rivets,
screws or weld joints on the vessel wall su-
perimpose their echoes to the product or
useful echo. Please ensure the sufficient
distance of the sensor to the vessel wall,
depending on the maximum measuring dis-
tance (dimension B in diagram).

In case of good reflection conditions (liquids,
no vessel installations), we recommend de-
termining the sensor distance according to

. At a max. meas. distance

of e.g. 10 m, the distance of the transducer
(according to curve 1) should be approx.
1.5 m.

In case of solids with poor reflective proper-
ties, determine the distance to the vessel wall
according to

. Under very

bad measuring conditions (rough vessel
walls, struts), it might be necessary to in-
crease the distance to the vessel wall, or to
also filter out the false echoes by storing
them in memory, thereby adapting the sensor
more precisely to the environment.

Advertising