VEGASON 51P … 53P

65

Setup

6.3 Sensor adjustment with the ad-

justment module MINICOM

-

+

ESC

OK

Tank 1

m (d)
12.345

In addition to the PC, you can adjust the
sensors with the small, detachable adjust-
ment module MINICOM directly in the sensor.

With the adjustment module MINICOM, only
the sensor-relevant adjustment such as e.g.
scaling of the sensor display, operating
range, meas. conditions, sensor display
scaling or false echo storage are possible.
However, not possible are all adjustment
steps relating to configuration, conditioning
and signal processing (configuration of the
inputs and outputs, linearisation curves,
simulation …). This is only possible with the
PC.

The adjustment module MINICOM is adjusted
with six keys. A small display shows you,
apart from the measured value, a short mes-
sage on the menu item or the entered value
of a menu adjustment.

The volume of information of the small display,
however, cannot be compared with that of the
adjustment program VVO, but with the help
of the menu schematic for MINICOM, you will
quickly find your way through the adjustment
structure. In time, you might even be able to
carry out your adjustments with the small
module faster and more efficiently than with
the PC.

Error codes:

E013

No valid measured value
- Sensor in the warm-up phase
- Loss of the useful echo

E017

Adjustment span too small

E036

Sensor program not operating
- Sensor must be reprogrammed

(service)

- Fault signal also appears during

programming

E040

Hardware failure, electronics

defective

Adjustment steps

On pages 70 and 71 you will find the com-
plete menu schematic of the adjustment mod-
ule MINICOM.
Set up the sensor in the numbered se-
quence:
1. Address
2. Measurement in gases
3. Operating range
4. Adjustment
5. Conditioning
6. Meas. conditions
7. False echo storage (only required when

errors occur during operation).

8. Indication of the useful and noise level
9. Outputs
Short explanations to the setup steps 1 … 9
follow.

1. Address

Choose a free bus address with the DIP
switch (see chapter "5.2 Sensor address“).