7 Output results

7.6.4 Rectangular weir with throat

With sharp weir edge and throat

Weir edge
K = 6290

Calculation of the actual flow value (Q)

The following formula can be used for calculation of the
actual flow for liquid levels < h

max

… > h

min

.

Q = B • K • h

1,5

Q in m

3

/h

B in m
h in m

Assumed values for a calculation example
B =

0,4 m

K =

6290

h =

0,13 m

Calculation example
Q =

0,4 • 6290 • 0,13

1,5

= 117,9 m

3

/h

Programming acc. to calculation example
Q

max

= 117,9 m

3

/h

- Mode

0 - 82

, flow = 0118

- Mode

0 - 83

, multiplier = 0

- Mode

0 - 84

, time unit = 3

Explanation:
Q

max

= max. flow in m

3

/h

B

= weir width in mm or m

K

= throat specific factor for above rectangular weir = 6290

h

max

= max. weir height in mm or m

k

= thickness of the weir in mm

3 - 4 x h

max

2 - 3 x h

max

2 x h

max

B

45

°

Selection of the actual flow (Q)

Flow schedule for usual rectangular weir

B

Q

max

h

max

Q

min

h

min

in mm in m

3

/h

in mm

in m

3

/h

in mm

200

52,3

120

18,5

60

300

109,6

150

27,7

60

400

295,8

240

37,0

60

500

441,2

270

46,2

60

600

620,0

300

55,5

60

800

1519

450

73,9

60

1000

2923

600

92,4

60

1500

6128

750

138,7

60

2000

13535

1050

184,9

60

3000

34666

1500

277,3

60

If a rectangular weir acc. to above value is used, the value
for Q

max

can be taken out of the respective column and can

be used for programming of mode

0 - 82

0 - 84

.

Programming acc. to selection Q

max

= 13535 m

3

/h

-

Mode

0 - 82

, flow = 1353

-

Mode

0 - 83

, multiplier = 1

-

Mode

0 - 84

, time unit = 3