7 Output results

7.7

Level module

The pulse-echo measuring system can be equipped with a
level module. This module is provided with two relays.

Mode coordination

Relay

Coordination

Switching command

output

ON

OFF

1

Mode 0 - 53

Mode 0 - 55

Mode 0 - 56

2

Mode 0 - 54

Mode 0 - 60

Mode 0 - 61

7.7.1 Coordinations and their relations

For each relay or relay output the coordination can be
programmed separately.

Relay

Measur-

Measur-

Coordination

Linearization

ing result

ing unit

Mode

Mode

1

Distance
in m

0 - 53 = 1

0 - 18 = 1

Level
in %

0 - 53 = 2

0 - 18 = 1

Volume

Flow

propor-

in %

0 - 53 = 2

0 - 18 =

tional

4 … 12

2

as above, however

0 - 54 = …

0 - 18 = …

7.7.2 Switching commands

Mode

0 - 53

defines the measuring result and its

measuring unit coordinated to the relay output.

Acc. to the sequence of the switching commands it is
possible to program the respective relay output as overfill
protection or protection against dry running of pumps
(A/B-function).

The min-

for the switching commands is 10 mm or 0,5 %.

Mode

0 - 55

means switching command on, i.e.

- the relay of output 1 is energized
- the LED-indication extinguishes

Mode

0 - 56

means switching command off, i.e.

- the relay of output 1 is de-energized
- the LED-indication lights

Same procedure for relay output 2, however mode

0 - 60

and

0 - 61

.

Diagram for overfill protection

Two point level switch: switching command off above
switching command on means overfill protection
(function A)

0

25

75

100

50

% m

off

on

0

25

75

100

50

% m

on

off

Programming example for relay output 1

-

coordination to measuring unit level in % corresponds
to

0 - 53

=

2

-

two-point level switch as overfill protection

Coordination

Enquire mode

0 - 53

in the MODEFIELD

Program figure

2

in the PARAMETER FIELD

Then store with STO

Switching command on

Enquire mode

0 - 55

in the MODEFIELD

Program

025.0

% in the PARAMETER FIELD

Then store with STO

Switching command off

Enquire mode

0 - 56

in the MODEFIELD

Program

050.0

% in the PARAMETER FIELD

Then store with STO

Same procedure for relay output 2, however mode

0 - 60

and

0 - 61

.

Level
propor-
tional

switching
command off
Mode 0 - 56

switching
command on
Mode 0 - 55

switching
command on
Mode 0 - 55

switching
command off
Mode 0 - 56

Diagram for protection against dry running of
pumps

Two point level switch: switching command off above
switching command on means protection against dry
running of pumps (function B)