8supplementary programmings, 1 failure processing, 8 current module – VEGA VEGASON 71 - D User Manual

Page 33

Advertising
background image

VEGASON 71 - D

33

7 Output results / 8 Supplementary programmings

8

Supplementary programmings

8.1

Failure processing

In mode

0 - 93

the reaction of the relay and current outputs

in case of failure can be defined.

Programming possibilites

Mode

Current outputs

Relay outputs

0 - 93

LED

= 1

actual currents are

no change

stored

= 2

current - 0 mA

= 3

current corresp. to 0 %

operated relay de-energize

= 4

current corresp. to 100%

Programming example

Change-over to failure processing
e.g.

0 - 93

=

4

• Enquire mode

0 - 93

in the MODEFIELD

• Program figure

4

in the PARAMETER FIELD

• Then store with STO

Note
For adjustment of the failure processing observe
additionally the schedule of error codes in the supplement.

7.8

Current module

The pulse-echo measuring system can be equipped with
another module. The module is provided with two current
outputs.

Current output 1 is automatically coordinated to the flow
proportional output result and current output 2 to the level
proportional output result.

The course of characteristics of the current output is fixed
by an initial and final point.

The factory setting defines a course of 4 … 20 mA
corresponding to 0 … 100 %.

Within the whole range of 0.00 … 20.00 mA, each current
value can be programmed for a raising or falling
characteristics.

The current-

between initial and final value must be min.

1 mA.

Programming example

Factory setting

Programming example

100

80

60

40

20

16

0

0

% mA

mA

20

4

End of characteristics 100 % ^ 16 mA

Enquire mode

0 - 65

in the MODEFIELD

Program

16.00

mA in the PARAMETER FIELD

Then store with STO

Begin of characteristics 0 % ^ 0 mA

Enquire mode

0 - 66

in the MODEFIELD

Program

00.00

mA in the PARAMETER FIELD

Then store with STO

Mode

0 - 66

Begin of
characteristics

Mode

0 - 65

End of
characte-
ristics

Advertising