9.3

Definition of the operating range

The operating range can be limited in this mode by
programming of
-

operating range begin and

-

operating range end.

Echoes outside this limitation are ignored.

Note

The operating range end should always be programmed
10 % > than the flume end.

9.4

Multiple echo reduction

It is possible to reduce the echo gain by an offset function
to gate out possible multiple echoes.

Reduction range (offset range) = 0.00 … 1.25
Practical values = 0.00 … 0.20

9 Optimization

9.5

Adjustment of the max. gain

The pulse-echo measuring system tries to detect an echo
by using the whole gain. This means, that in case of an
empty flume the gain can be bigger than required for the
useful echo when the flow is available.

This causes that sound reflections (false echoes) are
detected as useful echoes. It is useful to limit the control
range of the gain to avoid this.

Note
- The limitation can be adjusted from 0.03 V to 4.50 V, as

optimization up to 4.95 V.

- The optimum adjustment of this mode is only possible

when the flume is empty.

- For orientation a d is indicated on the display of the

measuring system, as long as with the actual gain, an
echo (false echo) is detected.

Programming example

Indication of the echo gain
• Enquire mode

1 - 20

in the MODEFIELD

• e.g.

2.00

is indicated in the PARAMETER FIELD, i.e. in

case of an obviously wrong indication of measured
values, a false echo is detected with a gain of

2.000

Limitation
• Enquire mode

1 - 21

in the MODEFIELD

• Program e.g.

2.30

as limitation in the PARAMETER

FIELD

• Then store with STO

Optimization
• Enquire mode

1 - 22

in the MODEFIELD

e.g. d

2.30

is displayed in the PARAMETER FIELD

• Activate the optimization with MOD-key
• Optimize with "+"-key, until d extinguishes

The optimization is made in 0.02 V steps.

Requirement for this adjustment is that with actually
available flow, a considerably higher gain is sufficient
(relate do above example

2,50 V).

If during the optimization a modification in the other
direction is required, this can be realized with key "–".

Useful echo

Multiple echoes

The reduction (offset) depends on the
function and starts with the end of the
measuring window.

Programming example

Reduction and optimization to e.g. 0.20

Reduction

Enquire mode

1 - 12

in the MODEFIELD

Program reduction

0.12

(V) in the PARAMETER FIELD

Then store with STO

Optimization

Enquire mode

1 - 13

in the MODEFIELD

Activate the optimization with MOD-key (the whole
parameter indication

0.12

flashes)

Optimize with "+"-key, until e.g.

0.20

(V)

The optimization is made in 0.01 V steps

If during the optimization a modification in the other
direction is required, this can be realized with key "–".