4 Mounting
VEGAFLEX 82 • 4 … 20 mA/HART two-wire
44222-EN-130823
1
2
Fig. 6: Installation in non-metallic vessel
1 Flange
2 Metal sheet
Concrete vessel
When installed in thick concrete ceilings, VEGAFLEX 82 should be
mounted front flush to the lower edge. In concrete silos, the distance
to the wall should be at least 500 mm (20 in).
ø >160 mm
(ø >6.3")
Fig. 7: Installation in concrete silo
If possible, avoid sockets. Mount the sensor flush with the vessel top.
If this is not possible, use short sockets with small diameter.
Socket