10 Diagnostics and service

VEGAFLEX 82 • 4 … 20 mA/HART two-wire

44222-EN-130823

After an electronics exchange the settings of the electronics must

be checked and verified. Only then, the instrument is again ready for

operation.

10.6 Exchange or shorten cable/rod

The cable or rod (meas. part) of the probe can be shortened, if neces-

sary. To loosen the rod or cable you need a fork spanner with spanner

width 13.
1. Loosen the rod or cable by applying a fork spanner to the flat

surfaces (SW 13), provide counterforce with another fork spanner

(SW 13)

2. Unscrew the loosened rod or cable manually.
3. Place the enclosed new double washer onto the thread.
Caution:

Make sure that the two components of the double washer remain

together.
4. Screw the new rod and the new cable manually to the thread on

the process fitting.

5. Exert counterforce with the second fork spanner and tighten the

or or cable on the flat surfaces with a torque of 15 Nm (11 lbf ft).

Fig. 41: Exchange cable or rod

Exchanging the cable/rod