7 Set up with the display and adjustment module

VEGAFLEX 82 • 4 … 20 mA/HART two-wire

44222-EN-130823

Note:

A false signal suppression is only recommended with liquid applica-

tions.
A false signal suppression detects, marks and saves these false sig-

nals so that they are no longer taken into account for level measure-

ment.
This should be done with the lowest possible level so that all potential

interfering reflections can be detected.
Proceed as follows:

Enter the actual distance from the sensor to the product surface.

All interfering signals in this section are detected by the sensor and

stored.
Note:

Check the distance to the product surface, because if an incorrect

(too large) value is entered, the existing level will be saved as a false

echo. The filling level would then no longer be detectable in this area.
If a false signal suppression has already been created in the sensor,

the following menu window appears when selecting "False signal

suppression":

The instrument carries out an automatic false signal suppression

as soon as the probe is uncovered. The false signal suppression is

always updated.
The menu item "Delete" is used to completely delete an already cre-

ated false signal suppression. This is useful if the saved false signal

suppression no longer matches the metrological conditions in the

vessel.

With this menu item you safeguard the sensor parameters against

unauthorized or unintentional modifications.
To avoid possible errors during parameterization in a non-safe user

environment, a verification procedure is used that makes it possible

to detect parameterization errors reliably. For this, safety-relevant

parameters must be verified before they are stored in the device. In

normal operating condition, the instrument is also locked against

parameter changes through unauthorized access.