7 Set up with the display and adjustment module
VEGAFLEX 82 • 4 … 20 mA/HART two-wire
44222-EN-130823
For the socket correction you have to enter the height of the socket
above the upper edge of the vessel. If the socket is lower than the up-
per edge of the vessel, this value can also be negative.
+
h
D
- h
Fig. 27: Vessel height und socket correction value
D Vessel height
+h Positive socket correction value
-h Negative socket correction value
Since scaling is very extensive, scaling of the level value was divided
into two menu items.
In menu item "Level 1" you define the scaling variable and the scaling
unit for the level value on the display, e.g. volume in l.
Setup - Scaling Level
Setup - Scaling Level 1