7 Set up with the display and adjustment module

VEGAFLEX 82 • 4 … 20 mA/HART two-wire

44222-EN-130823

signal suppression, user-programmable linearization curve as well as

the measured value memory will be deleted.
Basic settings: Resetting of the parameter settings incl. special

parameters to the default values (presettings) of the respective instru-

ment. Any created false signal suppression or user-programmable lin-

earization curve as well as the measured value memory are deleted.
The following tables show the default values of the instrument. De-

pending on the instrument version or application, all menu items may

not be available or some may be differently assigned.

The menu items in bold are safety-relevant in terms of the functional

safety according to IEC 61508 (Edition 2) SIL.

Setup

Menu item

Default value

Modified value

Lock adjustment

Locked

Measurement loop name

Sensor

Units

Distance unit: mm
Temperature unit: °C

Probe length

Length of the probe Ex factory

Medium type

Bulk solid

Application

Level in the metallic vessel

Medium, dielectric constant

Granules, powder, cement /

1.5 … 3

Superimposed gas phase

Yes

Dielectric constant, upper medium (TS)

1.5

Tube inner diameter

200 mm

Max. adjustment - Level

100 %

Max. adjustment - Level

Distance: 0.000 m(d) - note block-

ing distances

Min. adjustment - Level

0 %

Min. adjustment - Level

Distance: Probe length - take dead

band into account

Accept adjustment of the level measurement? Yes
Max. adjustment - Interface

100 %

Max. adjustment - Interface

Distance: 0.000 m(d) - note block-

ing distances

Min. adjustment - Interface

0 %

Min. adjustment - Interface

Distance: Probe length - take dead

band into account

Integration time - Level

0.0 s

Integration time - Interface

0.0 s

Linearization type

Linear

Linearization - Socket correction

0 mm