10 Diagnostics and service

VEGAFLEX 82 • 4 … 20 mA/HART two-wire

44222-EN-130823

Information:

Please keep the stated torque so that the max. tensile strength

remains.
6. Enter new probe length and if necessary the new probe type and

then carry out a fresh adjustment (see "Setup procedure, Carry-

ing out min. adjustment - Carrying out max. adjustment").

The rod or cable of the probe can be shortened individually.

1. Mark the requested length with mounted measuring rod.
2. Cable: Loosen the three pins on the gravity weight

Cable ø 4: 6 hexagon 3
Cable ø 6, cable ø 8: hexagon 4

3. Cable: remove the pins
4. Cable: Pull the cable out of the gravity weight
5. Shorten the cable/rod with a cut-off wheel or metal saw at the

marking. Take note of the specifications in the following illustration

when shortening the cable.

6. Cable: shift the cable into the gravity weight (according to the

drawing)
Plastic coated cable: remove coating according drawing to 70 mm

(2.76 in).

7. Cable: Fasten the cable with three pins, torque 20 Nm

(14.75 lbf in)
Cable ø 4: 7 Nm (5.16 lbf ft)
Cable ø 6, cable ø 8: 20 Nm (14.75 lbf ft)

8. Enter new probe length and then carry out a fresh adjustment

(see "Setup procedure, Carrying out min. adjustment - Carrying

out max. adjustment").

Shorten cable/rod