7 Set up with the display and adjustment module

VEGAFLEX 82 • 4 … 20 mA/HART two-wire

44222-EN-130823

The default setting is min. current 3.8 mA and max. current 20.5 mA.

If a supplementary electronics with a second current output is im-

plemented in the instrument, then you can adjust the second current

output separately.
In menu item"Current output 2" you specify which measured value

the second current output refers to.

The second current output cannot be used as an output in the sense

of a safety-instrumented application (SIL).
The procedure corresponds to the previous settings of the standard

current output. See "Setup - Current output".

Since the HART variables are very extensive, the indication was

divided into two menu items.
In the menu "HART variables 1" you can have the first HART value PV

(primary value) and the second HART value SV (secondary value) of

the sensor displayed.
The values cannot be changed in the display and adjustment module.

To change these values, you have to use the adjustment software

PACTware.
HART functions are not relevant for SIL applications.

In the menu "HART variables 2" you can have the third HART value

TV (third value) and the fourth HART value QV (quarter value) of the

sensor displayed.
The values cannot be changed in the display and adjustment module.

To change these values, you have to use the adjustment software

PACTware.
HART functions are not relevant for SIL applications.

The following circumstances cause interfering reflections and can

influence the measurement:

High sockets

Vessel installations such as struts

Deflectors, etc.

Setup - Current output 2

Setup - HART variables

(1)

Setup - HART variables

(2)

Setup - False signal sup-

pression