Quick start

VEGAFLEX 82 • 4 … 20 mA/HART two-wire

44222-EN-130823

2. In the menu item "Medium - Dielectric constant" you can define

the medium type (medium).

3. Carry out the adjustment in the menu items "Min. adjustment" and

"Max. adjustment".

4. A "Linearization" is recommended for all vessels in which the

vessel volume does not increase linearly with the level - e.g. in a

horizontal cylindrical or spherical tank. Activate the appropriate

curve.

The sensor measures the distance from the sensor (reference plane)

to the product surface.

4

5

3

1

2

4

1

2

3

5

Fig. 3: Measuring ranges - VEGAFLEX 82
1 Reference plane

2 Probe length L

3 Measuring range

4 Upper dead band (in this area no measurement is possible)

5 Lower dead band (in this area no measurement is possible)

For this adjustment, the distance is entered when the vessel is full

and nearly empty. If these values are not known, an adjustment with

other distances, for example, 10 % and 90 % is also possible. Starting

point for these distance specifications is always the seal surface of

the thread or flange.
1. In the menu "Additional settings", menu item "Damping" you can

adjust the requested damping of the output signal.

2. Select the parameter of the current output and the output charac-

teristics in the menu item "Current output".

Parameterization example

Further steps