7 Set up with the display and adjustment module
VEGAFLEX 82 • 4 … 20 mA/HART two-wire
44222-EN-130823
You have the option of choosing the demonstration mode. In this
mode, the sensor ignores the parameters of the application and
reacts immediately to any change.
This mode is only suitable for test and demonstration purposes and
must not be used in a safety-instrumented application (SIL).
In this menu item, you can define the medium type (product).
This menu item is only available if you have selected level measure-
ment under the menu item "Application".
You can choose between the following medium types:
Dielectric figure Product type
Examples
> 3
Cereals, flour
All kind of cereals, wheat flour
1.5 … 3
Granules, cement Lime, gypsum, cement
< 1.5
Dusts, wood chips Wood chips, sawdust
In this menu item, you can enter the max. adjustment for the level.
Adjust the requested percentage value with [+] and store with [OK].
Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. The distance refers to the sensor
reference plane (seal surface of the process fitting). Keep in mind that
the max. level must lie below the dead band.
In this menu item, you can enter the min. adjustment for the level.
Setup - Medium, dielec-
tric constant
Setup - Max. adjustment
Level
Setup - Min. adjustment
Level