7 Set up with the display and adjustment module
VEGAFLEX 82 • 4 … 20 mA/HART two-wire
44222-EN-130823
Verify parameter
All safety-relevant parameters must be verified after a change. After
the function test, all modified, safety-relevant parameters will be
listed. Confirm the modified values one after the other.
If the described process of parameter adjustment was run through
completely and correctly, the instrument will be locked and hence
ready for operation.
Otherwise the instrument remains in the released and hence unsafe
condition.
If you have to interrupt the function test, you can leave the display and
adjustment module of VEGAFLEX 82 in its current state.
As long as VEGAFLEX 82 is powered, the display and adjustment
module remains in the currently set adjustment menu.
To interrupt the function test, you have to push the button "ESC".
If you carry out the function test by means of the "PACTware" soft-
ware, you can store the previously performed tests and continue from
there later on.
In the main menu point "Display", the individual submenu points
should be selected subsequently and provided with the correct
parameters to ensure the optimum adjustment of the display options.
The procedure is described in the following.
The following submenu points are available:
The submenu points described below.
This menu item enables the setting of the requested national lan-
guage.
In the delivery status, the sensor is set to the ordered national lan-
guage.
Display
Display - Menu language