VEGA VEGAFLEX 82 4 … 20 mA_HART two-wire Rod and cable probe With SIL qualification User Manual

Page 36

Advertising
background image

36

7 Set up with the display and adjustment module

VEGAFLEX 82 • 4 … 20 mA/HART two-wire

44222-EN-130823

Setup: Settings, e.g. measurement loop name, medium, vessel,

adjustment, signal output, device unit, false signal suppression,

linearization curve
Display: Settings, e.g., for language, measured value display, lighting
Diagnosis: Information, e.g. on instrument status, pointer, measure-

ment reliability, simulation, echo curve
Additional adjustments: Reset, date/time, reset, copy function
Info: Instrument name, hardware and software version, date of manu-

facture, instrument features
Note:

For optimum adjustment of the measurement, the individual submenu

items in the main menu item "Setup" should be selected one after

the other and provided with the correct parameters. If possible, go

through the items in the given sequence.
The procedure is described below.
The following submenu points are available:

The submenu points described below.
Adjustment process

A parameter change with SIL qualified instruments must always be

carried out as follows.

Release adjustment

Change parameter

Lock adjustment and verify modified parameters

This ensures that all modified parameters were consciously changed.
Release adjustment

The instrument is shipped in locked condition.
As a protection against unintentional or unauthorized adjustment, the

instrument is locked against all parameter changes in normal operat-

ing condition.
For each parameter change you have to enter the PIN of the instru-

ment. In delivery status, the PIN is "0000".

If adjustment is enabled, the safety function must be considered

as unreliable. This applies until the parameterization is terminated

Advertising