7 Set up with the display and adjustment module
VEGAFLEX 82 • 4 … 20 mA/HART two-wire
44222-EN-130823
For this reason, the instrument is shipped in locked conditon. The PIN
in the delivery status is "0000".
Character string comparison and serial number
You first have to carry out the character string comparison. This is
used to check the character respresentation.
Confirm if the two character strings are identical. The verification texts
are provided in German and with all other menu languages in English.
Afterwards you confirm that the serial number of your instrument was
carried over correctly. This is used to check device communication.
In the next step, the instrument checks the data of the measurement
and decides by means of the evaluation results if a functions test
is required. If a function test is necessary, the following message is
displayed.
In this case, you have to carry out a function test.
Function test
During a function test, you have to test the safety function of the
instrument in the vessel with the original medium.
For this purpose, you should know the filling height of the vessel as
well as the min. and max. levels respectively for 4 and 20 mA. You
then can calculate the respective output current.
Measure the output current of VEGAFLEX 82 with a suitable multi-
meter and compare the measured output current with the calculated
output current.
You have to determine the permissible deviation of the values
yourself. This deviation depends on the the accuracy requirements of
your measurement loop. Determine the permissible tolerance for the
deviation.
If you have to interrupt the function, you can leave the VEGAFLEX 82
in the respective situation.
As long as VEGAFLEX 82 is powered, the display and adjustment
module remains in the currently set adjustment menu.
To interrupt the function test, you have to push the button "ESC".
If you carry out the function test by means of the "PACTware" soft-
ware, you can store the previously performed tests and continue from
there later on.