background image

29

6 Functional safety (SIL)

VEGAFLEX 82 • 4 … 20 mA/HART two-wire

44222-EN-130823

4 … 20 mA current output

6.4 Safety concept of the parameterization

The following tools are permitted for parameterization of the safety

function:

The integrated display and adjustment unit for on-site adjustment

The DTM suitable for the signal conditioning instrument in con-

junction with an adjustment software according to the FDT/DTM

standard, e. g. PACTware

Note:

For operation of the VEGAFLEX 82 the DTM Collection version 1.67.2

or higher is required. The modification of safety-relevant parameters is

only possible with active connection to the instrument (online mode).

To avoid possible errors during parameterization in a non-safe user

environment, a verification procedure is used that makes it possible

to detect parameterization errors reliably. For this, safety-relevant pa-

rameters must be verified after they are stored in the device. In normal

operating condition, the instrument is also locked against parameter

changes through unauthorized access. This concept applies to the

adjustment on the instrument but also to adjustment with PACTware

with DTM.

For protection against unwanted or unauthorzed adjustment, the set

parameters must be barred from unauthorized access. For this rea-

son, the instrument is shipped in locked condition. The PIN in delivery

status is "0000".
When shipped with a specific parameter adjustment, the instruments

are accompanied by a list with the values deviating from the basic set-

ting. By entering the serial number, the list is available as a download

under "www.vega.com/VEGA-Tools".
All safety-relevant parameters must be verified after a change.
The parameter settings of the measurement loop must be document-

ed. You can find a list of all safety-relevant paramters in the shipping

status in chapter "Setup with the display and adjustment module"

under "Additional settings - Reset". In addition, a list of the safety-

relevant parameters can be stored and printed via PACTware/DTM.

For each parameter change, the instrument must be unlocked via a

PIN (see chapter "Setup steps - Lock adjustment"). The device status

is indicated by the symbol of an unlocked or locked padlock.
In delivery status, the PIN is 0000.

Warning:

If adjustment is enabled, the safety function must be considered

as unreliable. This applies until the parameterization is terminated

correctly. If necessary, other measures must be taken to maintain the

safety function.

Tool for operation and

parameterization

Reliable parameterization

Safety-relevant param-

eters

Release adjustment

Unsafe device

status