10 Diagnostics and service

VEGAFLEX 82 • 4 … 20 mA/HART two-wire

44222-EN-130823

Code
Text mes-

sage

Cause

Rectification

C700
Simulation ac-

tive

– A simulation is active

– Finish simulation

– Wait for the automatic end

after 60 mins.

C701
Parameter

verification

– Parameter verification was

interrupted

– Finish parameter verifica-

tion

The following table shows the error codes and text messages in the

status message "Out of specification" and provides information on

causes as well as corrective measures.

Code
Text mes-

sage

Cause

Rectification

S600
Unpermissi-

ble electronics

temperature

– Temperature of the elec-

tronics in the non-specified

section

– Check ambient temperature

– Isolate electronics

– Use instrument with higher

temperature range

S601
Overfilling

– Danger of vessel overfilling

– Make sure that there is no

further filling

– Check level in the vessel

The following table shows the error codes and text messages in the

status message "Maintenance" and provides information on causes

as well as corrective measures.

Code
Text mes-

sage

Cause

Rectification

M500
Error with the

reset delivery

status

– With the reset to delivery

status, the data could not

be restored

– Repeat reset

– Load XML file with sensor

data into the sensor

M501
Error in the

non-active

linearization

table

– Hardware error EEPROM

– Exchanging the electronics

– Send instrument for repair

M502
Error in the

diagnosis

memory

– Hardware error EEPROM

– Exchanging the electronics

– Send instrument for repair

Out of specification

Maintenance